5 Commissioning the device

27

2014-05-01

5

Commissioning the device

5.1

Display and operating elements

h

Connect the voltage supply - a test routine will start during which all LEDS will flash and the display with background light-

ing will indicate white pixels for 2 seconds and black pixels for 2 seconds.

Once the test routine has been completed, the device will indicate the main measured value (factory set).

v

If an alarm or error message appears, refer to Chapter 10 "Alarm messages".

5.2

Setting the display after switch-on

v

Chapter 7.6.4 "Normal display"

The screen is factory set to show the main measured value in German. The example shows the screen layout of a safety tem-

perature limiter monitoring a maximum value of 29.6°C with a pre-alarm set to 9.9°C.

H

If the main measured value is within the hysteresis during "Power ON", the relay outputs "Pre-alarm" and "Alarm"

are deactivated.

1 Switching behavior

2 Device function
3 Binary input

7 Main measured value

6 Pre-alarm

4 Temperature unit

5 Limit value

(1)

(2)

(3)

(4)

(5)

(6)

(7)