6 Safety Manual
42
6.8.2
Failure rates and SFF for 701150...25 (AC/DC 24 V)
Important information:
Variants 1 to 4 were evaluated with JUMO probes according to data sheets 901006 and 902006.
For variant 5 no sensor system was taken into account.
In this case, the user selects the sensor system.
The PFH and PFD
avg
values were calculated with the assumption that the time to restore the system is 8 h (MTTR = 72 h). Fur-
thermore, the calculation was based on a lifetime of 10 years (T
1
= 10 y). The Common Cause Factor was determined accord-
ing to the tables of DIN EN 61508 for sensor systems and logic.
Variant
λ
s
[Fit]
λ
dd
[Fit]
λ
dd
[Fit]
SFF
PFH (1/h)
PFD
avg
1
799.3
306.32
33.61
96 %
6.59 e
-9
2.91 e
-4
1a
799.3
306.32
33.61
96 %
3.07 e
-9
1.35 e
-4
2
802.26
303.36
33.61
96 %
3.07 e
-9
1.35 e
-4
3
827.25
324.71
37.91
96 %
3.13 e
-9
1.37 e
-4
4
833.31
341.75
39.81
96 %
3.23 e
-9
1.41 e
-4
5
818.96
323.07
36.26
96 %
3.05 e
-9
1.33 e
-4