10 determining the achieved performance level pl, 1 terms and abbreviations acc. to din en iso 13849, 6 safety manual – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 48

Advertising
background image

6 Safety Manual

2014-05-01

48

6.10 Determining the achieved Performance Level PL

The following safety-related parameters are required to determine the Performance Level of components/devices:

As further parameters to be observed, operational aspects such as the demand rate and/or the test rate of the safety function

can also influence the resulting PL.
Excerpt from DIN EN ISO 13849-1:2008-12

6.10.1

Terms and abbreviations acc. to DIN EN ISO 13849

Planned operating duration

10 years

Architecture according to DIN EN ISO

13849-1

Sensor system, one-channel: Cat. 2

Sensor system, two-channel: Cat. 3

MTTF

d

-DC

avg

according to DIN EN

ISO 13849-1 table K.1

PL d:

62 years DC

avg

60 %

PL e:

62 years DC

avg

90 %

Mode of operation and software

class according to DIN EN 14597

JUMO STB/STW 701150 possesses the following mode of operations

2B, 2D, 2F, 2K, 2J, 2V, 2N, 2P software class C

H

This excerpt contains references to the complete standard DIN EN ISO 13849-1:2008-12, which are therefore not

reproduced in this chapter.

Formula symbol or
abbreviation

Description

Definition
or location

PL (a, b, c, d, e)

Description for the Performance Level

Table 3

Safety feature

Requirement / comment