7 Configuration level
78
Max. alarm:
If the measured value exceeds the limit value, the alarm
relay output switches OFF. The LEDs K1 and K2 light
up red and the measured values flash in the display.
If set to the safety temperature limiter (STB) setting, this condition remains even when the main
measured value is back in the valid range. Only when the "Reset" key is pressed or a switch is
activated when the binary input is respectively configured will the alarm relay output switch on
again and the OK LED light up green.
When setting the safety temperature monitor (STW), the alarm relay output automatically
switches back to ON as soon as the main measured value is back within the valid range.
Parameter
Comment
Value range
(factory-setting in bold)
Limit value
S
P
14
16
15
Ö
3,15A
S
P
14
16
15
Ö
3,15A
Min. set.range
Max. set.range
Hyster
esis
Relay output Alarm aktive
Relay output Alarm inactive
S
P
11
12
13
Ö
Max. alarm
(older devices: inverse or O-Function)
Distance from limit value
Pre-alarm range
Measured value
Measured value
Alarm range
Valid range
Pre-alarm (absolute value)
Hyster
esis
Relay output pre-alarm
active
KV
Relay output pre-alarm
KV inactive
LED KV lights up yellow
LED OK lights up green
LED K1, K2 lights up red