2 analog output, Analog output, Binary input – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 90: Relay outputs, 8 technical data

8 Technical data
90
8.2
Analog output
8.3
Binary input
8.4
Relay outputs
Type of sig-
nal
Accuracy
Residual ripple
Load influence
Temperature
influ-
ence
Load
resis-
tance
Current
4 to 20 mA
≤
0.5 %
± 0.5 % at 300
Ω
± 0.05 mA/ 100
Ω
150 ppm / K
≤
500
Ω
0 to 20 mA
Voltage
2 to 10 V
≤
0.5 %
± 0.5 %
± 15 mV
150 ppm / K
≥
500
Ω
0 to 10 V
Connection
Function
1 potential-free contact
Unlocking, keyboard locking, level locking can be configured
Relay output KV
Relay (changeover contact) without shroud
30000 operations at a performance of 3 A /250 V, 50 Hz resistive load
or maximum DC 30 V / 3 A. Minimal current: DC 12 V / 100 mA.
Relay output alarm
Changeover contact
Contact protection switching:
safety fuse 3.15 AT, installed in the N/O contact arm
30000 operations at a performance of 3 A /230 V, 50 Hz resistive load
or maximum DC 30 V / 3 A. Minimal current: DC 12 V / 100 mA.