8 technical data, Technical data, Analog inputs – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 88

8 Technical data
88
8 Technical
data
8.1
Analog inputs
RTD temperature probe
Thermocouples
Designation Measuring
range
Accuracy
2/3-wire circuit
1
Ambient temperature
influence
Pt100
DIN EN 60751
-200 to +850 °C
0.5% / 0.1%
50 ppm/K
Pt1000
DIN EN 60751
-200 to +850 °C
0.5% / 0.1%
50 ppm/K
Connection type
2-wire, 3-wire circuit
Maximum output resistance 30
Ω
Measuring rate
210
ms
Error tolerance time
≤
5s time taken into account for all diagnosis tests
Input filter
Digital filter, 2nd priority; filter constant can be set from 0 to 100 s
Special features
Individual probe Pt100 2-wire,
display can also be programmed in °F
Designation Measuring
range
Accuracy
1
Ambient temperature
influence
Fe-CuNi "L"
DIN 43710
-200 to +900 °C
0.4%
100 ppm/K
Fe-CuNi "J"
DIN EN 60584
-200 to +1200 °C
0.4%
100 ppm/K
Cu-CuNi "U"
DIN 43710
-200 to +600 °C
0.4%
100 ppm/K
Cu-CuNi "T"
DIN EN 60584
-200 to +400 °C
0.4%
100 ppm/K