Installation, 3 connection diagram, Observe the following when using e.l.c.b – Lenze SMD 0-37kW-22kW Full I/O User Manual

Page 12

Advertising
background image

12

Lenze 13466183 EDBSC03 v7

Installation

Observe the following when using E.l.c.b:

Installation of E.l.c.b only between supplying mains and controller.

The E.l.c.b can be activated by:

capacitive leakage currents between the cable screens during operation (especially with

long, screened motor cables)

connecting several controllers to the mains at the same time

RFI filters

3.2.3 Connection Diagram

U V W

L1 L2 L3

PE

N

L3

L2

L1

3/PE 320V - 0 % … 528V + 0 %

48 Hz … 62 Hz

0.5 Nm/ 4.5 lb-in

6 mm /0.24 in

0.2 Nm/ 2 lb-in

6 mm /0.24 in

< 1mm

2

/AWG 26…16

_

L1 L2

PE

N

L3

L2

L1

3/PE 180V - 0% … 264V + 0 %

48 Hz … 62 Hz

L3

1.2 Nm/ 10 lb-in

9 mm /0.35 in

2.0 Nm/ 18 lb-in

13 mm /0.5 in

L2/N

PE

N

L3

L2

L1

2/PE 180V - 0% … 264V + 0 %

48 Hz … 62 Hz

L1

PE

N

L3

L2

L1

1/N/PE 180V - 0% … 264V + 0 %

48 Hz … 62 Hz

L2/N

L1

PES

PE

PES

PES

M

3~

PES

PE

20

9

8

7

28

E1 E2 E3 7 62 K14 K12

+12V

+10V

AI

N

CO

M

CO

M

AOUT

7

28

E1 E2

7 8

E3

-

+

+12 VDC - 0 %

+30 VDC + 0 %

0 … 20 mA

4 … 20 mA

GND L H

CAN

C0002

DANGER!

• Hazard of electrical shock! Circuit potentials are up to 240 VAC above earth

ground. Capacitors retain charge after power is removed. Disconnect power and

wait until the voltage between B+ and B- is 0 VDC before servicing the drive.

• Do not connect mains power to the output terminals (U,V,W)! Severe damage to

the drive will result.

• Do not cycle mains power more than once every three minutes. Damage to the

drive will result.

WARNING!

Per UL requirements, use a FUSE (not a circuit breaker) for 240VAC drives requiring

>40A protection and for 480VAC & 600VAC drives requiring >32A protection.

Advertising
This manual is related to the following products: