Commissioning – Lenze SMD 0-37kW-22kW Full I/O User Manual

Page 16

Advertising
background image

16

Lenze 13466183 EDBSC03 v7

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

CE1 Configuration -

Digital input E1

1

1 Activate fixed setpoint 1 (JOG1)

2 Activate fixed setpoint 2 (JOG2)

• Use C37...C39 to adjust fixed setpoints

• Activate JOG3: Both terminals = HIGH

3 DC braking (DCB)

See also C36

4 Direction of rotation

LOW = CW rotation

HIGH = CCW rotation

5 Quick stop

Controlled deceleration to standstill, active

LOW; Set decel rate in C13

6 CW rotation

CW rotation = LOW and CCW rotation =

LOW: Quick stop; Open-circuit protected

CE2 Configuration -

Digital input E2

4

7 CCW rotation

8 UP (setpoint ramp-up)

9 DOWN (setpoint ramp-down)

UP = LOW and DOWN = LOW: Quick

stop; Use momentary NC contacts

10 TRIP set

Active LOW, triggers EEr (motor coasts

to standstill)

NOTE:

NC thermal contact from the motor

can be used to trigger this input

11 TRIP reset

See also c70

12 No action

can be used if Ex inputs are used only as

CANopen digital inputs

CE3 Configuration -

Digital input/output

E3

3

1...12 (same as above)

13...19 (reserved)

20 Ready

21 Fault

22 Motor is running

23 Motor is running - CW rotation

24 Motor is running - CCW rotation

25 Output frequency = 0 Hz

26 Frequency setpoint reached

27 Threshold (C17) exceeded

• 1...11 configures terminal E3 as an input

• 20...30 configures terminal E3 as a

current-sourcing (PNP) output rated 12

VDC / 50 mA

28 Current limit reached

• in either motor or generator mode

29 Dynamic Braking
30 CANopen Control

• output controlled by RPDO (h66,h76 = 4)

NOTE

A CFG fault will occur under the following conditions:

• E1...E3 settings are duplicated (each setting can only be used once)

• One input is set to UP and another is not set to DOWN, or vice-versa

C08 Configuration -

Relay output

(terminals K14 and

K12)

1

Relay is energized if
0 Ready

1 Fault

2 Motor is running

3 Motor is running - CW rotation

4 Motor is running - CCW rotation

5 Output frequency = 0 Hz

6 Frequency setpoint reached

7 Threshold (C17) exceeded

8 Current limit reached

in either motor or generator mode

9 CANopen Control

Output controlled by RPDO (h66,h76 = 4)

C10 Minimum output

frequency

0.0 0.0 {Hz} 240 • Output frequency at 0% analog setpoint

• C10 not active for fixed setpoints or

setpoint selection via c40