Commissioning – Lenze SMD 0-37kW-22kW Full I/O User Manual

Page 19

Advertising
background image

Lenze 13466183 EDBSC03 v7

19

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

c20 I

2

t switch-off (thermal

motor monitoring)

100 30 {%} 100

100% = smd rated output current

• Triggers 0C6 fault when motor current

exceeds c20 for too long

• Correct setting = (motor nameplate

current) / (smd output current rating) X

100%

Example: motor = 6.4 amps and smd =

7.0 amps; correct setting = 91%

(6.4 / 7.0 = 0.91 x 100% = 91%)

WARNING!

Maximum setting is rated motor current (see nameplate). Does not provide full

motor protection!

c21 Motor Overload Type

00

00 Speed Compensation

Reduces the allowable continuous

current when operating below

30Hz.

Ir

100%

60%

30 f

1

0

Ir: rated current (%), f: motor frequency (Hz)

01 No Speed Compensation

Example: Motor is cooled by forced

ventilation as apposed to shaft

mounted, self cooling fans.

c40 Frequency setpoint

via keys

0.0 0.0

{Hz}

240 Only active if C01 = 1

c42 Start condition

(with mains on)

1

0 Start after LOW-HIGH change at

terminal 28

See also c70

1 Auto start if terminal 28 = HIGH

WARNING!

Automatic starting/restarting may cause damage to equipment and/or injury to

personnel! Automatic starting/restarting should only be used on equipment that is

inaccessible to personnel.

c60 Mode selection

for c61

0

0 Monitoring only

c60 = 1 allows the keys

to adjust

speed setpoint (c40) while monitoring c61

1 Monitoring and editing

c61 Present status/error

status/error message

Display

• Refer to Section 5 for explanation of

status and error messages

c62 Last error

error message

c63 Last error but one
c70 Configuration TRIP

reset (error reset)

0

0 TRIP reset after LOW-HIGH change

at terminal 28, mains switching, or

after LOW-HIGH change at digital

input “TRIP reset”

1 Auto-TRIP reset

Auto-TRIP reset after the time set in c71

More than 8 errors in 10 minutes will

trigger rSt fault

WARNING!

Automatic starting/restarting may cause damage to equipment and/or injury to

personnel! Automatic starting/restarting should only be used on equipment that is

inaccessible to personnel.

c71 Auto-TRIP reset delay

0.0 0.0

{s}

60.0 See c70

c78 Operating time

counter

Display: Total time in status “Start”

0...999 h: format xxx

1000...9999 h: format x.xx (x1000)

10000...99999 h: format xx.x (x1000)

c79 Mains connection

time counter

Display: Total time of mains = on