Safety Information

Note for UL approved system with integrated controllers

UL warnings are notes which apply to UL systems. The documentation contains special information

about UL.

Warnings!

• Integral solid state protection does not provide branch circuit protection. Branch

circuit protection must be provided in accordance with the National Electrical

Code and any additional local codes. The use of fuses or circuit breakers is the

only approved means for branch circuit protection.

• When protected by CC and T Class Fuses, suitable for use on a circuit capable of

delivering not more than 200,000 rms symmetrical amperes, at the maximum

voltage rating marked on the drive.

• Additionally suitable when protected by a circuit breaker having an interrupting

rating not less than 200,000 rms symmetrical amperes, at the maximum

voltage rating marked on the drive. (Excludes ESMD113_4T_, ESMD112_2Y_,

ESMD113_2T_, ESMD152_2Y_, ESMD153_2T_, ESMD222_2Y_, ESMD223_4T_,

ESMD402_2T_, ESMD552_2T_, ESMD752_2T_, ESMD153_4T_, and ESMD183_4T_).

• Use minimum 75°C copper wire only, except for control circuits.
• For control circuits, use wiring suitable for NEC Class 1 circuits only.
• Torque Requirements are listed in section 3.2.3, Connection diagram.
• Shall be installed in a pollution degree 2 macro-environment.

DANGER!

Risk of Electric Shock! Capacitors retain charge for approximately 180 seconds

after power is removed. Disconnect incoming power and wait at least 3 minutes

before touching the drive.

DANGER!

Risque de choc électrique! Les condensateurs restent sous charge pendant environ

180 secondes après une coupure de courant. Couper l’alimentation et patienter

pendant au moins 3 minutes avant de toucher l’entraînement.

WARNING!

The opening of branch-circuit protective device may be an indication that a fault

has been interrupted. To reduce the risk of fire or electric shock, current carrying

parts and other components of the controller should be examined and replaced if

damaged.

AVERTISSEMENT!

Le déclenchement du dispositif de protection du circuit de dérivation peut être dы

а une coupure qui résulte d’un courant de défaut. Pour limiter le risque d’incendie

ou de choc électrique, examiner les pièces porteuses de courant et les autres

éléments du contrôleur et les remplacer s’ils sont endommagés