Commissioning – Lenze SMD 0-37kW-22kW Full I/O User Manual

Page 17

Advertising
background image

Lenze 13466183 EDBSC03 v7

17

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

C11 Maximum output

frequency

50.0 7.5 {Hz} 240 • Output frequency at 100% analog

setpoint

• C11 is never exceeded

WARNING!

Consult motor/machine manufacturer before operating above rated frequency.

Overspeeding the motor/machine may cause damage to equipment and injury

to personnel!

C12 Acceleration time

5.0 0.0 {s} 999 • C12 = frequency change 0 Hz...C11

• C13 = frequency change C11...0 Hz

• For S-ramp accel/decel, adjust c82

C13 Deceleration time

5.0 0.0 {s} 999

C14 Operating Mode

2

0 Linear characteristic with

Auto-Boost

• Linear characteristic: for standard

applications

• Square-law characteristic: for fans

and pumps with square-law load

characteristic

• Auto boost: load-dependent output

voltage for low-loss operation

1 Square-law characteristic with

Auto-Boost

2 Linear characteristic with constant

V

min

boost

3 Square-law characteristic with

constant V

min

boost

C15 V/f reference point

50.0 25.0 {Hz} 999

Set the rated motor frequency

(nameplate) for standard applications

smd006

C16 V

min

boost

(optimization of

torque behavior)

4.0 0.0 {%} 40.0

Set after commissioning: The unloaded

motor should run at slip frequency

(approx. 5 Hz), increase C16 until

motor current (C54) = 0.8 x rated motor

current

C17 Frequency threshold

(Q

min

)

0.0 0.0 {Hz} 240 See C08, selection 7

Reference: setpoint

C18 Chopper frequency

2

0 4 kHz

• As chopper frequency is increased,

motor noise is decreased

• Observe derating in Section 2.2

• Automatic derating to 4 kHz at 1.2 x I

r

1 6 kHz
2 8 kHz
3 10 kHz

C21 Slip compensation

0.0 0.0 {%} 40.0 Change C21 until the motor speed no

longer changes between no load and

maximum load

C22 Current limit

150 30 {%} 150

Reference: smd rated output current

• When the limit value is reached, either

the acceleration time increases or the

output frequency decreases

• When C90 = 2, max setting is 180%

C24 Accel boost

0.0 0.0 {%} 20.0 Accel boost is only active during

acceleration

C34 Configuration -

analog input

0

0 0...10 V
1 0...5 V
2 0...20 mA
3 4...20 mA

C36 Voltage - DC

injection brake

(DCB)

4.0 0.0 {%} 50.0

See CE1...CE3 and c06

• Confirm motor suitability for use with DC

braking