Commissioning

4.2

Electronic Programming Module (EPM)

The EPM contains the controller’s memory. Whenever parameter settings are changed,

the values are stored in the EPM. It can be removed, but must be installed for the

controller to operate (a missing EPM will trigger an F1 fault). The controller ships with

protective tape over the EPM that can be removed after installation.

An optional EPM Programmer (model EEPM1RA ) is available that allows: the controller to be

programmed without power; OEM settings to be default settings; fast copying of EPMs when multiple

controllers require identical settings. It can also store up to 60 custom parameter files for even faster

controller programming.

C0003

Tmd007

4

Commissioning

4.1

Parameter Setting

Status/fault messages

Change parameters

NOTE

If the password function is enabled, the password must be entered into C00 to

access the parameters. C00 will not appear unless the password function is enabled.

See C94.