Commissioning – Lenze SMD 0-37kW-22kW Full I/O User Manual

Page 24

Advertising
background image

24

Lenze 13466183 EDBSC03 v7

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

TPDO#1 configuration parameters

h80

(1)

TPDO#1 COB ID

385 0 2047 If h53 = 0, 2: Setting will change to

384 + Node ID during power-up or h58

reset.

h81

(1)

TPDO#1 enable/

disable

1

0 Disable
1 Enable (no RTR)
2 Enable (with RTR)

Enable individual polling of TPDO#1

h82 TPDO#1

transmission type

255 0 255

h82 = 0...240: Transmit TPDO#1 after

every n

th

SYNC received + Event + RTR

(if enabled)

h82 = 253: Event + RTR (if enabled)

h82 = 254: COS triggered (WORD0 of

TPDO#1) + Event + RTR (if enabled)

h82 = 255: Event + RTR (if enabled)

h83

(1)

TPDO#1 inhibit time

50

0

{0.1 ms}

65535 Sets minimum time between TPDO#1

transmissions (h83 = 50 = 5.0 ms)

h84 TPDO#1 event timer

0

0

{ms}

65535

Sets the fixed interval for TPDO#1

transmission

h84 = 0: disables event timer

h86

(1)

TPDO#1 mapping

(see TPDO mapping

details)

0

0 C0150 + C50 signed

C50 scaling: + 50 = + 1.0 Hz

1 C0150 + C50 unsigned

C50 scaling: 10 = 1.0 Hz

2 Controller status in C0135 format +

frequency setpoint signed

Can be used to control other controllers

(see example in section 4.5)

3 Controller status in C0135 format +

frequency setpoint unsigned

4 402 Device profile: Statusword

0x6041

5 402 Device profile: Statusword

0x6041 + vl control effort 0x6044

vl control effort units = signed RPM

RPM calculation based on C87 and C89

6 C0150 + C50 signed and scaled +

digital input + analog input

C50 scaling: +/- 16384 = C11

h87 TPDO#1 WORD0

bit mask

65535

0

65535

COS (change of state) bit mask applied

to WORD0 of TPDO selected by h86.

h87 = 65535: activates all bits of

WORD0 for COS triggering

h87 = 0: disables COS triggering

h89 TPDO#1 status

0 255

Read-only

Number of transmitted TPDO#1

messages

Above 255, starts over at 0

(1)

These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”