Lenze 13466183 EDBSC03 v7

15

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

C00 Password entry

0

0 999 Visible only when password is active

(see C94)

C01 Setpoint and control

source

0

Setpoint source:

Control configuration:

0 Analog input (terminal 8; see C34)

Control = terminals

Programming = keypad/limited CANopen

Monitoring = CANopen

Note:

RPDOs not processed in these

modes

1 Code c40

2 CANopen

Control = terminals

Programming = CANopen/keypad

Monitoring = CANopen

Note:

Only frequency setpoint part of

RPDOs are processed in this mode

3 CANopen

Control = CANopen

Programming = CANopen/keypad

Monitoring = CANopen

C02 Load Lenze setting

0 No action/loading complete

• C02 = 1...4 only possible with

OFF or 1nh

• C02 = 2 : C11, C15 = 60 Hz

1 Load 50 Hz Lenze settings

2 Load 60 Hz Lenze settings

3 Load OEM settings (if present)

4 Translate

WARNING!

C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled! Check codes

CE1...CE3.

NOTE

If an EPM that contains compatible data from a previous software version is

installed, C02 = 4 converts the data to the current version.