Commissioning

WORD0 - C0135 control word

Bit

h66 / h76 setting = 0

WORD0 - C0135 control word

Bit

h66 / h76 setting = 1

0

JOG1, JOG2, JOG3

0 = C46 active

1 = JOG1 (C37) active

2 = JOG2 (C38) active

3 = JOG3 (C39) active

0

JOG1, JOG2, JOG3

0 = C46 active

1 = JOG1 (C37) active

2 = JOG2 (C38) active

3 = JOG3 (C39) active

1

1

2

Direction of rotation

0 = CW (forward)

1 = CCW (reverse)

2

Direction of rotation

0 = CW (forward)

1 = CCW (reverse)

3

Quick stop

0 = Quick stop not active

1 = Quick stop active

3

Quick stop

0 = Quick stop not active

1 = Quick stop active

4

reserved

4

reserved

5

reserved

5

reserved

6

reserved

6

reserved

7

reserved

7

reserved

8

reserved

8

reserved

9

Controller inhibit

0 = No controller inhibit

1 = Controller inhibit

9

Controller inhibit

0 = No controller inhibit

1 = Controller inhibit

10

reserved

10

reserved

11

TRIP reset

TRIP reset on transition from 0 to 1

11

TRIP reset

TRIP reset on transition from 0 to 1

12

reserved

12

reserved

13

reserved

13

reserved

14

DC brake

0 = DC brake not active

1 = DC brake active

14

DC brake

0 = DC brake not active

1 = DC brake active

15

reserved

15

reserved

WORD1

Signed frequency setpoint written to C46

Frequency setpoint [Hz] = WORD1 value / 50

Example 1: Requested setpoint = CW at 34.5 Hz

= 34.5 x 50 = 1725 = 0x06BD

Example 2: Requested setpoint = CCW at 44.5

Hz = - (44.5 x 50) = -2225 = 0xF74F

Note:

Setpoint sign overrides Bit 2 in WORD0

WORD1

Unsigned frequency setpoint written to C46

Frequency setpoint [Hz] = WORD1 value / 10

Example: Requested setpoint = CW at 34.5 Hz =

34.5 x 10 = 0x0159

Direction is set by bit 2 in WORD0

WORD2

reserved (not evaluated)

WORD3

reserved (not evaluated)