Commissioning – Lenze SMD 0-37kW-22kW Full I/O User Manual

Page 18

Advertising
background image

18

Lenze 13466183 EDBSC03 v7

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

C37 Fixed setpoint 1

(JOG 1)

20.0 0.0 {Hz} 240

C38 Fixed setpoint 2

(JOG 2)

30.0 0.0 {Hz} 240

C39 Fixed setpoint 3

(JOG 3)

40.0 0.0 {Hz} 240

C46 Frequency setpoint

0.0 {Hz} 240 Display: Setpoint via CANopen, analog

input, or function UP/DOWN

C50 Output frequency

0.0 {Hz} 240 Display

C53 DC bus voltage

0.0 {%} 255 Display

C54 Motor current

0.0 {%} 255 Display

C87 Motor rated speed

1390 300 {RPM} 32000 Set to motor nameplate speed

C89 Motor rated

frequency

50

10 {Hz} 1000 Set to motor nameplate frequency

C90 Input voltage

selection

0 Auto

Automatically sets to Low (1) or High (2)

upon next power-up, depending on input

voltage

1 Low

For 200 V or 400 V input

2 High

For 240 V or 480 V input

NOTE

• To simplify commissioning, the Lenze setting is preset at the factory, depending on

model:

C90 = 1 for 400/480 V models

C90 = 2 for 230/240 V models

• Upon reset (C02 = 1, 2), C90 = 0. Confirm correct setting after next power-up.

C94 User password

0

0 999
Changing from “0” (no password), value

will start at 763

When set to a value other than 0,

must enter password at C00 to access

parameters

C99 Software version

Display, format: x.yz

c06 Holding time -

automatic DC

injection brake

(Auto-DCB)

0.0 0.0

{s}

999

0.0 = not active

999 = continuous brake

Automatic motor braking below 0.1 Hz

by means of motor DC current for the

entire holding time (afterwards: U, V, W

inhibited)

Confirm motor suitability for use with DC

braking

c08 Analog output

scaling

100 1.0

999 When 10 VDC is output at terminal 62, it

will equal this value (see c11)

c11 Configuration -

Analog output (62)

0

0 None
1 Output frequency 0-10 VDC

Use c08 to scale signal
Example:

c11 = 1 and c08 = 100:

At 50 Hz, terminal 62 = 5 VDC

At 100 Hz, terminal 62 = 10 VDC

2 Output frequency 2-10 VDC
3 Load 0-10 VDC
4 Load 2-10 VDC
5 CANopen Control

Value set by RPDO (h66,h76 = 4)

(c08 not used for scaling)