Commissioning – Lenze SMD 0-37kW-22kW Full I/O User Manual

Page 22

Advertising
background image

22

Lenze 13466183 EDBSC03 v7

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

RPDO#1 configuration parameters

h60

(1)

RPDO#1 COB ID

513 0 2047 If h53 = 0, 2: Setting will change to

512 + Node ID during power-up or h58

reset.

h61

(1)

RPDO#1 enable/

disable

1

0 Disable
1 Enable

h62 RPDO#1

transmission type

255 0 255

h62 = 0...240: transfer on every SYNC

received.

h62 = 254, 255: immediate transfer

h64 RPDO#1 event

monitoring timer

0

0

{ms}

65535 h64 = 0: monitoring disabled

h65 RPDO#1 time out

reaction

0

0 Not active

Only active when C01 = 3

1 Inhibit
2 Quick stop
3 Trip fault FC3

h66

(1)

RPDO#1 mapping

(see RPDO mapping

details)

0

0 C0135 control word + C46 signed

C46 scaling: + 50 = + 1.0 Hz

1 C0135 control word + C46 unsigned C46 scaling: 10 = 1.0 Hz

2 402 Drives and Motion Control:

PDO Controlword 0x6040

3 402 Drives and Motion Control:

PDO Controlword 0x6040 +

vl target velocity 0x6042

vl target velocity units = signed RPM

RPM calculation based on C87 and C89

4 C0135 Controlword +

C46 signed and scaled +

Digital output + analog output

C46 scaling: +/- 16384 = C11

h69 RPDO#1 status

0 255

Read-only

Number of received RPDO#1 messages

Above 255, starts over at 0

(1)

These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”