30

Lenze 13466183 EDBSC03 v7

Commissioning

WORD0 - Controller status in C0135 format

Bit

h86 / h96 setting = 2

WORD0 - Controller status in C0135 format

Bit

h86 / h96 setting = 3

0

JOG1, JOG2, JOG3

0 = C46 active

1 = JOG1 (C37) active

2 = JOG2 (C38) active

3 = JOG3 (C39) active

0

JOG1, JOG2, JOG3

0 = C46 active

1 = JOG1 (C37) active

2 = JOG2 (C38) active

3 = JOG3 (C39) active

1

1

2

Direction of rotation

0 = CW (forward)

1 = CCW (reverse)

2

Direction of rotation

0 = CW (forward)

1 = CCW (reverse)

3

Quick stop

0 = Quick stop not active

1 = Quick stop active

3

Quick stop

0 = Quick stop not active

1 = Quick stop active

4

reserved

4

reserved

5

reserved

5

reserved

6

reserved

6

reserved

7

reserved

7

reserved

8

reserved

8

reserved

9

Controller inhibit

0 = No controller inhibit

1 = Controller inhibit

9

Controller inhibit

0 = No controller inhibit

1 = Controller inhibit

10

reserved

10

reserved

11

TRIP reset

0 = No TRIP reset

1 = TRIP reset

11

TRIP reset

0 = No TRIP reset

1 = TRIP reset

12

reserved

12

reserved

13

reserved

13

reserved

14

DC brake

0 = DC brake not active

1 = DC brake active

14

DC brake

0 = DC brake not active

1 = DC brake active

15

reserved

15

reserved

WORD1

Signed frequency setpoint [Hz]

Scaling = frequency setpoint [Hz] x 50

Example 1: CW at 34.5 Hz = 34.5 x 50 = 1725 =

0x06BD

Example 2: CCW at 44.5 Hz = - (44.5 x 50) = -

2225 = 0xF74F

WORD1

Unsigned frequency setpoint [Hz]

Scaling = frequency setpoint [Hz] x 10

Example: CW at 34.5 Hz = 34.5 x 10 = 345 =

0x0159

Direction is indicated by bit 2 in WORD0

WORD2

reserved

WORD3

reserved

Advertising