9

Installation

EMC

Compliance with EN 61800-3/A11

Noise emission

Compliance with limit value class A according to EN 55011 if installed in a control

cabinet with the appropriate footprint filter and the motor cable length does not

exceed 10m

A Screen clamps
B Control cable

C Low-capacitance motor cable

(core/core < 75 pF/m, core/screen < 150 pF/m)

D Electrically conductive mounting plate
E Filter

Tmd005

B

C

D

A

E

3.2.2 Fuses/cable cross-sections

3.2

Electrical installation

3.2.1 Installation according to EMC requirements

(1)

Type

Recommendations

E.l.c.b.

(2)

Fuse

Miniature

circuit

breaker

(5)

Fuse

(3)

or

Breaker

(6)

Input Power Wiring

(L1, L2/N, L3, PE)

(N. America)

[mm²]

[AWG]

1/N/PE

ESMD371L2YXA

M10 A

C10 A

10 A

2.5

14

> 30 mA

ESMD751L2YXA

M16 A

C16 A

15 A

2.5

14

ESMD112L2YXA

M20 A

C20 A

20 A

4

(4)

12

ESMD152L2YXA

M25 A

C25 A

25 A

6

(4)

12

ESMD222L2YXA

M32 A

C32 A

30 A

4

10

3/PE

ESMD371L2YXA ... ESMD751L2YXA

ESMD371L4TXA ... ESMD222L4TXA

M10 A

C10 A

10 A

2.5

14

ESMD112L2YXA, ESMD152L2YXA

ESMD302L4TXA

M16 A

C16 A

12 A

2.5

14

ESMD222L2YXA

M16 A

C16 A

15 A

2.5

12

ESMD402L4TXA

M16 A

C16 A

15 A

2.5

14

ESMD302L2TXA

ESMD552L4TXA

M20 A

C20 A

20 A

4

(4)

12

ESMD402L2TXA

ESMD752L4TXA

M25 A

C25 A

25 A

6

(4)

10

ESMD552L2TXA

ESMD113L4TXA

M40 A

C40 A

35 A

6

8

ESMD752L2TXA

ESMD153L4TXA

M50 A

C50 A

45 A

10

8

ESMD183L4TXA

M63 A

C63 A

60 A

16

6

ESMD113L2TXA

ESMD223L4TXA

M80 A

C80 A

70 A

16

6

ESMD153L2TXA

M100 A

C100 A

90 A

16

4

(1) Observe the applicable local regulations.

(2) Pulse-current or universal-current sensitive earth leakage circuit breaker.

(3) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R, JJN, JJS or equivalent.

(4) Connection without end ferrules or with attached pin end connectors.

(5) Installations with high fault current due to large supply mains may require a type D circuit breaker.

(6) Thermomagnetic type breakers preferred.