Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

C00

Password entry

0

0 999 Visible only when password is active

(see C94)

C01

Setpoint and control

source

0

Setpoint source:

Control configuration:

0 Analog input (terminal 8; see C34) Control = terminals

Programming = keypad

Monitoring = LECOM

1 Code c40

2 Analog input (terminal 8; see C34) Control = terminals

Programming = LECOM / keypad

Monitoring = LECOM

3 LECOM

Control = LECOM

Programming = LECOM / keypad

Monitoring = LECOM

4 Analog input (terminal 8; see C34) Control = terminals

Programming = remote keypad

Monitoring = remote keypad

5 Code c40

6 Analog input (terminal 8; see C34) Control = remote keypad

Programming = remote keypad

Monitoring = remote keypad

7 Code c40

8 Analog input (terminal 8; see C34) Control = terminals

Programming = Modbus / keypad

Monitoring = Modbus

9 Code c40

10 Analog input (terminal 8; see C34) Control = Modbus

Programming = Modbus / keypad

Monitoring = Modbus

11 Code c40

Note

• When C01 = 1, 5, 7, 9, or 11, use c40 for speed setpoint

• When C01 = LECOM (3), write speed command to C46

C02

Load Lenze setting

0 No action/loading complete

• C02 = 1...4 only possible with

OFF

or

1nh

• C02 = 2 : C11, C15 = 60 Hz

1 Load 50 Hz Lenze settings

2 Load 60 Hz Lenze settings

3 Load OEM settings (if present)

4 Translate

WARNING!
C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled! Check codes

CE1...CE3.
NOTE

If an EPM that contains data from a previous software version is installed, C02 =

4 converts the data to the current version.

4.3

Parameter menu