Installation

Observe the following when using E.l.c.b:

• Installation of E.l.c.b only between supplying mains and controller.

• The E.l.c.b can be activated by:

- capacitive leakage currents between the cable screens during operation (especially with long,

screened motor cables)

- connecting several controllers to the mains at the same time

- RFI filters

Installation After a Long Period of Storage

STOP!

Severe damage to the drive can result if it is operated after a long period of storage or

inactivity without reforming the DC bus capacitors.

If input power has not been applied to the drive for a period of time exceeding three years

(due to storage, etc), the electrolytic DC bus capacitors within the drive can change

internally, resulting in excessive leakage current. This can result in premature failure of

the capacitors if the drive is operated after such a long period of inactivity or storage.

In order to reform the capacitors and prepare thedrive for operation after a long period of

inactivity, apply input power to the drive for 8 hours prior to actually operating the motor.

3.2.3 Connection diagram

U V W

L1 L2

8 9 20 28 E1 E2 E3

K14 K12

+10 V

+12 V

COM

AIN

7

8

7

+

_

71 72

L3

7

28 E1 E2 E3

20 A1 62

AOUT

TXA

TXB

COM

DIGOUT

PE

N

L3

L2

L1

3/PE 320V - 0 % … 528V + 0 %

48 Hz … 62 Hz

0.5 Nm/ 4.5 lb-in

6 mm /0.24 in

0.2 Nm/ 2 lb-in

6 mm /0.24 in

< 1mm? /AWG 26…16

_

0 … 20 mA

4 … 20 mA

1k … 10k

+12 V DC - 0 %

+30 V DC + 0 %

L1 L2

PE

N

L3

L2

L1

3/PE 180V - 0% … 264V + 0 %

48 Hz … 62 Hz

L3

1.2 Nm/ 10 lb-in

9 mm /0.35 in

2.0 Nm/ 18 lb-in

13 mm /0.5 in

L2

PE

N

L3

L2

L1

2/PE 180V - 0% … 264V + 0 %

48 Hz … 62 Hz

L1

PE

N

L3

L2

L1

1/N/PE 180V - 0% … 264V + 0 %

48 Hz … 62 Hz

L2

L1

PES

PE

PES

PES

M

3~

PES

PE

smd403

WARNING!

Per UL requirements, use a FUSE (not a circuit breaker) for 240VAC drives requiring >40A

protection and for 480VAC & 600VAC drives requiring >32A protection.

DANGER!

• Hazard of electrical shock! Circuit potentials are up to 240 VAC above earth ground.

Capacitors retain charge after power is removed. Disconnect power and wait until the

voltage between B+ and B- is 0 VDC before servicing the drive.

• Do not connect mains power to the output terminals (U,V,W)! Severe damage to the

drive will result.

• Do not cycle mains power more than once every three minutes. Damage to the drive

will result.