Trouble shooting & fault elimination, 5troubleshooting and fault elimination – Lenze SMD 0-37kW-22kW User Manual

Page 22

Advertising
background image

20

Lenze 13466184 EDBSL03 v20

EN, DE, FR, IT, ES

Trouble Shooting & Fault Elimination

Status

Cause

Remedy

e.g.

50.0

Present output frequency

Trouble free operation

OFF

Stop

(outputs U, V, W inhibited)

LOW signal at terminal 28

Set terminal 28 to HIGH

1nh

Inhibit

(outputs U, V, W inhibited)

Controller is set up for remote

keypad or serial control (see C01)

Start the controller via the remote

keypad or serial link

stP

Output frequency = 0 Hz

(outputs U, V, W inhibited)

Setpoint = 0 Hz (C31 = 0)

Setpoint selection

Quick stop activated through digital

input or serial link

Deactivate Quick stop

br

DC-injection brake active

DC-injection brake activated

• via digital input

• automatically

Deactivate DC-injection brake

• digital input = LOW

• automatically after holding time

c06 has expired

CL

Current limit reached

Controllable overload

Automatically (see C22)

LU

Undervoltage on DC bus

Mains voltage too low

Check mains voltage

dEC

Overvoltage on DC bus during

deceleration (warning)

Excessively short deceleration time

(C13, c03)

Automatically if overvoltage
< 1 s,

OU

, if overvoltage > 1 s

nEd

No access to code

Can only be changed when the
controller is in

OFF

or

1nh

Set terminal 28 to LOW or inhibit

by serial link

rC

Remote keypad is active

Attempt to use buttons on front of

controller

Buttons on front of controller are

disabled when remote keypad is

active

Error

Cause

Remedy

(1)

cF

Data on EPM not valid

Data not valid for controller

• Use EPM providing valid data

• Load Lenze setting

CF

Data error

GF

OEM data not valid

F1

EPM error

EPM missing or defective

Power down and replace EPM

CFG

Digital inputs not

uniquely assigned

E1...E3 assigned with the same

digital signals

Each digital signal can only be

used once

Either just “UP” or “DOWN” used

Assign the missing digital signal to

a second terminal

dF

Dynamic braking fault

Dynamic braking resistors are

overheating

Increase deceleration time

EEr

External error

Digital input “TRIP set” is active

Remove external error

Internal fault

Please contact Lenze

FC3

Communication error

Serial timer has timed out

Check serial link connections

FC5

Communication error

Serial communication failure

Please contact Lenze

JF

Remote keypad fault

Remote keypad disconnected

Check remote keypad connections

LC

Automatic start inhibited

c42 = 0

LOW-HIGH signal change at

terminal 28

5

Troubleshooting and fault elimination

(1) The drive can only be restarted if the error message has been reset; see c70

F2...F0