Commissioning – Lenze SMD 0-37kW-22kW User Manual

Page 18

Advertising
background image

16

Lenze 13466184 EDBSL03 v20

EN, DE, FR, IT, ES

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

C31

Analog input dead

band

0

0 Enabled

C31 = 0 activates dead band for analog

input. When analog signal is within dead

band, controller’s output = 0.0 Hz and
display will read

StP

1 Disabled

C34

Configuration -

analog input

0

0 0...10 V
1 0...5 V
2 0...20 mA
3 4...20 mA
4 4...20 mA monitored

Will trigger

SD5

fault if signal falls below

2 mA

C36

Voltage - DC

injection brake

(DCB)

4.0 0.0 {%} 50.0

• See CE1...CE3 and c06

• Confirm motor suitability for use with

DC braking

C37

Fixed setpoint 1

(JOG 1)

20.0 0.0 {Hz} 999 When PI is active (see d38), C37...C39

are fixed PI setpoints

C38

Fixed setpoint 2

(JOG 2)

30.0 0.0 {Hz} 999

C39

Fixed setpoint 3

(JOG 3)

40.0 0.0 {Hz} 999

C46

Frequency setpoint

0.0 {Hz} 500 Display: Setpoint via analog input,

function UP/DOWN, or LECOM

C50

Output frequency

0.0 {Hz} 500 Display

C53

DC bus voltage

0.0 {%} 255 Display

C54

Motor current

0.0 {%} 255 Display

C59

PI feedback

c86 {%} c87 Display

C70

Proportional gain

5.0 0.0 {%} 99.9

C71

Integral gain

0.0 0.0 {s} 99.9

C90

Input voltage

selection

0 Auto

Automatically sets to Low (1) or High

(2) upon next power-up, depending on

input voltage

1 Low

For 200 V or 400 V input

2 High

For 240 V or 480 V input

Note

• To simplify commissioning, the Lenze setting is preset at the factory, depending

on model:

C90 = 1 for 400/480 V models

C90 = 2 for 230/240 V models

• Upon reset (C02 = 1, 2), C90 = 0. Confirm correct setting after next power-up.

C94

User password

0

0 999

Changing from “0” (no password),

value will start at 763

When set to a value other than 0,

must enter password at C00 to access

parameters

C99

Software version

Display, format: x.yz

c01

Acceleration time 2

5.0 0.0

{s}

999 • Activated using CE1...CE3

• c01 = frequency change 0 Hz...C11

• c03 = frequency change C11...0 Hz

• For S-ramp accel/decel, adjust c82

c03

Deceleration time 2

5.0 0.0

{s}

999