Commissioning – Lenze SMD 0-37kW-22kW User Manual

Page 20

Advertising
background image

18

Lenze 13466184 EDBSL03 v20

EN, DE, FR, IT, ES

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

c25

Serial baud rate

0

0 LECOM: 9600 bps

Modbus: 9600,8,N,2

• See C01

• LECOM if C01 = 0...3

• Modbus if C01 = 8...11

1 LECOM: 4800 bps

Modbus: 9600,8,N,1

2 LECOM: 2400 bps

Modbus: 9600,8,E,1

3 LECOM: 1200 bps

Modbus: 9600,8,O,1

c38

Actual PI setpoint

c86 c87 Display

c40

Frequency setpoint

via keys

or Modbus

0.0 0.0

{Hz}

500 Only active if C01 is set properly

(C01 = 1,5,7,9,11)

c42

Start condition

(with mains on)

1

0 Start after LOW-HIGH change at

terminal 28

See also c70

1 Auto start if terminal 28 = HIGH

WARNING!

Automatic starting/restarting may cause damage to equipment and/or injury to

personnel! Automatic starting/restarting should only be used on equipment that is

inaccessible to personnel.

c60

Mode selection for c61

0

0 Monitoring only

c60 = 1 allows the keys

to adjust

speed setpoint (c40) while monitoring c61

1 Monitoring and editing

c61

Present status/error

status/error message

• Display

• Refer to Section 5 for explanation of

status and error messages

c62

Last error

error message

c63

Last error but one

c70

Configuration TRIP

reset (error reset)

0

0 TRIP reset after LOW-HIGH

change at terminal 28, mains

switching, or after LOW-HIGH

change at digital input “TRIP reset”

1 Auto-TRIP reset

• Auto-TRIP reset after the time set in

c71

• More than 8 errors in 10 minutes will

trigger

rSt

fault

WARNING!

Automatic starting/restarting may cause damage to equipment and/or injury to

personnel! Automatic starting/restarting should only be used on equipment that is

inaccessible to personnel.

c71

Auto-TRIP reset delay 0.0 0.0

{s}

60.0 See c70

c78

Operating time

counter

Display
Total time in status “Start”

0...999 h: format xxx

1000...9999 h: format x.xx (x1000)

10000...99999 h: format xx.x (x1000)

c79

Mains connection

time counter

Display
Total time of mains = on

c81

PI setpoint

0.0 c86 c87

c82

S-ramp integration

time

0.0 0.0 {s} 50.0 • c82 = 0.0: Linear accel/decel ramp

• c82 > 0.0: Adjusts S-ramp curve for

smoother ramp

c86

Minimum feedback

0.0 0.0 999 • Select feedback signal at C34

• If feedback is reverse-acting, set

c86>c87

c87

Maximum feedback

100 0.0 999