Electrical installation

Wiring to a host

6

EDKMF2178IB DE/EN/FR 6.0

57

l

H2 VerdrahtLeitrechner−Belegung_Steckerleiste_2178

Wiring to a host

{

Danger!

An additional electrical isolation is required if a safe electrical isolation
(reinforced insulation) to EN 61800−5−1 is necessary.

For this purpose for instance an interface module for the master computer with an
additional electrical isolation can be used (see respective manufacturer information).

For wiring observe the electrical isolation of the supply voltage. The supply voltage is on the
same potential as the data bus.

The 5−pole plug connector with double screw connection serves to
ƒ connect the bus (

^ 58);

ƒ effect the external voltage supply (

^ 65).

CAN_L SHLD

V+

CAN_H

GND

120W

2178CAN003

Fig. 3

5−pole plug connector with double screw connection

Designation

Explanation

GND

Reference potential for external voltage supply
CAN−GND connection

CAN_L

Data line / input for terminating resistor 120

W

SHIELD

Shielding

CAN_H

Data line / input for terminating resistor 120

W

V+

External voltage supply