Commissioning

Possible settings via DIP switch

EDKMF2178IB DE/EN/FR 6.0

66

l

H1inbet−HINW_Einst_aktivieren_KommModule

7

Commissioning

Possible settings via DIP switch

The front panel DIP switches serve to set:
ƒ The node address (switches 1 ... 7)
ƒ The baud rate (switches 8 ... 10)

The Lenze setting of all DIP switches is OFF.

)

Note!

Settings via codes

ƒ

In the Lenze setting ˘ Address switches 1 ... 7 = OFF ˘, the values are
accepted from the codes C1850/C2350 (node address) and C1851/C2351
(baud rate).
– Node addresses > 99 can only be set via DIP switch.
– The baud rates 10 kbps and 20 kbps can only be selected via DIP switch.

ƒ

Writing the codes (e.g. with GDC via CAN) has a direct effect on the
standard device codes C0009 and C0126.

ƒ

Acceptance of code changes by:
– Switching off and then on again the voltage supply,
– "Reset node" with C0358 = 1;
– Network management command "Reset Communication";
– Set C2120 (AIF control byte) = 1.

ƒ

The codes are inactive if at least one address switch (1 ... 7) has been set to
ON position before a renewed mains connection.