Electrical installation

Wiring of system bus (CAN)

EDKMF2178IB DE/EN/FR 6.0

62

l

h2_can−Bus−Leitungslaenge_2178

Checking the use of repeaters

Compare the values derived from Tab. 1 Total cable length (

^ 60) and Tab. 2 Segment

cable length (

^ 61).

ƒ If the sum of the segment cable lengths is smaller than the total cable length to be

implemented, either repeaters must be used or the cable cross−section must be
increased.

ƒ If the use of repeaters reduces the max. possible total cable length so much that it is

smaller than the total cable length to be implemented, then the cable cross−section
must be increased or less repeaters must be used or the baud rate must be
decreased.

ƒ The use of a further repeater is recommended as ...

– service interface

Advantage: Trouble−free connection during bus operation is possible.

– calibration interface

Advantage: The calibration/programming unit remains electrically isolated.

Example

Given

Total cable length to be implemented

450 m

Number of nodes

32

Cable cross−section

0.50 mm

2

(AWG 20)

Baud rate

125 kbps

Repeater used

Lenze repeater EMF2176IB

Reduction of the max. total cable
length per repeater (EMF2176IB)

30 m

Results

Max. total cable length

630 m
(see Tab. 1 Total cable length (

^ 60))

Max. segment cable length

360 m
(see Tab. 2 Segment cable length (

^ 61))

Comparison

The max. segment cable length is smaller than the total
cable length to be implemented.

Conclusion

A repeater must be installed at the determined max.
segment cable length of 360 m.