Electrical installation

Wiring of system bus (CAN)

EDKMF2178IB DE/EN/FR 6.0

60

l

h2_can−Bus−Leitungslaenge_2178

Bus cable length

)

Note!

ƒ

It is absolutely necessary to comply with the permissible cable lengths.

ƒ

If the total cable lengths of the CAN nodes differ for the same baud rate,
the smaller value must be used to determine the max. cable length.

ƒ

Observe the reduction of the total cable length due to the signal delay of
the repeater.

Total cable length

The baud rate determines the total cable length.

Baud rate [kbps]

Max. bus length [m]

10

7450

20

3950

50

1550

125

630

250

290

500

120

1000

25

Tab. 1

Total cable length