9 diagnostics, Led status displays, Diagnostics – Lenze EMF2178IB User Manual

Page 77

Advertising
background image

Diagnostics

LED status displays

9

EDKMF2178IB DE/EN/FR 6.0

77

l

H1_Diagnose−statusanzeige−DriveLED

9

Diagnostics

LED status displays

Pos.

Status display (LED)

Description

0

Connection status to standard device, two−colour LED (green/red)

OFF

l

The communication module is not supplied with voltage.

l

The external voltage supply is switched off.

GREEN

Blinking

The communication module is supplied with voltage, but has
no connection to the standard device.
Cause:
The standard device is ...

l

switched off;

l

in the initialisation phase;

l

not available.

Constantly ON

The communication module is supplied with voltage and is
connected to the standard device.

RED

Constantly ON

CANopen operation impossible.

Blinking

Permanently:

l

Parameters are reset to Lenze setting.

l

CANopen operation possible.

1 x blinking:

l

An error occurred while saving a value.

2 x blinking:

l

CANopen operation possible.

l

The node address/baud rate from C1850/C2350 or
C1851/C2351 could not be accepted .