Electrical installation

Important notes

5



22

BA 33.0003 EN 1.0

5

Electrical installation

5.1

Important notes



Danger!

Hazardous voltage at the power terminals, even if the plug is removed:

residual voltage > 60 V!
Before working at the power terminals, disconnect the drive controller from

the mains and wait until the motor stands still (voltage at the contact while

the motor is turning).

General

z

Observe the notes in the terminal box of the motor.

z

Firmly tighten all connections.

z

Connect PE connector to earthing screw.

z

Fit connecting cable with strain relief.

z

Carefully earth the motor.

Voltage

supply

Servo spindle

motors

z

Servo spindle motors must be fed by servo inverters.

z

Connect the integrated encoder at the motor side with the

corresponding connections of the servo inverter.

Holding brake

(optional)

z

DC supply according to nameplate data of the brake or supply with AC

voltage via upstream rectifier (only spring-operated brake, PM brakes

205 V)

1)

z

Brakes for 205 V can be fed from the 230 V mains via bridge rectifiers,

brakes for 103 V from the 115 V mains.

z

Do not supply brakes with half-wave rectifiers from the AC system.

Inverter

operation

z

Observe the connection notes in the corresponding operating

instructions.

z

Ensure that motor and inverter are correctly assigned.

z

In particular, observe the speed limits and winding load. *

Cable cross

sections

z

Correctly dimension the connecting cables to avoid impermissible

heating.

z

Maintain minimum cross sections to DIN 57100 and secure

appropriately (see Tab. 1).

Motor

protection

Protection against

overload

z

Common current-dependent motor protection switches for average

operating frequency

– Set to rated current as indicated on the nameplate.

z

With very high operating frequency: Use three-phase AC motors from

Lenze with thermal switches or PTC thermistors in the winding.

– The thermal switches are integrated in the winding as NO contact or

NC contact. The response temperature is permanently set.

Motor supply cable

z

No protection possible via overtemperature protector switches or PTC

thermistors of the motor winding

– Take measures according to DIN 57100 / VDE 0530.

Inverter operation

z

The current or voltage conversion can increase the output current

significantly above the input current.

– The motor supply cable cannot be fused via the mains input fuses of

the inverter. Take measures according to DIN 57100 / VDE 0530.

1) Supply PM brakes for 24 VDC only with smooth DC voltage (ripple ≤1%)

*

Voltage limits: 1.5 kV peak value, 5 kV/µs rate of rise; additional information: see the data sheet.