Commissioning

6



27

BA 33.0003 EN 1.0

Servo controller ECS
The input and output variables of the speed controller are normalised to the maximum

current I

max.

(C0022) and the maximum speed n

max

(C0011). This allows C0022 and C0011

to directly influence the gain of the speed controller Vpn.
ƒ The following applies to the servo controller ECS:

– Vpn proportional n

max.

(C0011)

– Vpn proportional 1/I

max.

(C0022)

Parameter setting of motor temperature detection



Stop!

ƒ The integrated overload protection does not prevent overload under

all conditions!

ƒ Reduce maximum current to required value!

The motor winding temperature is monitored by thermal detectors.

Function block interconnection



Stop!

Perform function block interconnection (servo inverter 9300) or I

2

xt

monitoring (servo inverter ECS) with disconnection after several seconds of

operation with I > I

N

, particularly in case of danger of blocking.

Example for the function block interconnection for MDSLSWW056-33

I

O

= 4.0 A, C22 (I

max.

) = 10.5 A ⇒ C472/1 = 16%

IACT

(IACT)^2

I^2>

Ilimit

472/1

Trip set

Display:

z

Input value of PT1: C0642

z

Output value of PT1: C0689/1

z

Limit value: C0689/2

Calculation of limit value (FCODE 472/1):

FCODE472∕1 = (I

o

⋅ 1

I

⋅ 1.05)

2

⋅ 100

I

o

[A]

Standstill current of motor

FCODE472∕1 = (I

o

I

max.

1.05)

100

I

max.

[A]

Maximum current set under code C22

Factor 1.05: for consideration of manufacturing tolerances and reaching the standstill

torque; disconnection at I>1.05*I

0

Time constant PT1: C0640 (currently 30 s)