Ampacity of insulated cables by protective devices

1)

(DIN 57100 / VDE 0100 T 523)

Rated

Group 1

2)

Group 2

3)

Group 3

4)

cross

section q

[

2

]

Cable

Protective device

5)

Cable

Protective device

5)

Cable

Protective device

5)

[mm

2

]

I

N

[A]

I

N

[A]

I

N

[A]

I

N

[A]

I

N

[A]

I

N

[A]

Cu

Al

Cu

Al

Cu

Al

Cu

Al

Cu

Al

Cu

Al

0,75

1,0

1,5

11

15

6

10

12

15

18

6

10

10

15

19

24

10

10

20

20

25

33

20

25

33

15

20

26

16

20

25

10

16

20

26

34

44

20

27

35

20

25

35

16

20

25

32

42

54

26

33

42

25

35

50

20

25

35

45

61

83

45

61

83

36

48

65

35

50

63

25

35

50

61

82

108

48

64

85

50

63

80

35

50

63

73

98

129

57

77

103

63

80

100

50

63

80

35

50

70

103

132

165

81

103

80

100

125

63

80

135

168

207

105

132

163

100

125

160

80

100

125

158

198

245

124

155

193

125

160

200

100

125

160

95

120

150

197

235

160

200

250

292

335

197

230

263

200

250

250

160

200

200

292

344

391

230

268

310

250

315

315

200

200

250

Tab. 1

Ampacity;

maximum ambient temperature: 30 °C

1)

With adjustable protective devices (motor protection switch, circuit breaker). Adjust the

device to the rated cable current. Select cable circuit breaker according to DIN 57641 /

VDE 0641 / CEE 19 and protective cable fuses according to DIN 57636 / VDE 0636 in

accordance with the table.

2)

One or several single-core cables installed in a pipe

3)

Multi-core cables, e.g. plastic-sheathed cables, hardmetal-sheathed cables, lead-sheathed

cables, flat webbed cables, movable cables

4)

Single-core, freely installed cables where the spacing corresponds to at least their diameter

5)

With adjustable protective devices (motor protection switch, circuit breaker). Adjust the

device to the rated cable current. Select cable circuit breaker according to DIN 57641 / VDE

0641 / CEE 19 and protective cable fuses according to DIN 57636 / VDE 0636 in accordance

with the table.