9300 servo plc, Appendix – Lenze DDS Target 9300 Servo PLC V8.x User Manual

Page 118

Advertising
background image

9300 Servo PLC

Appendix

3−112

L

9300 Servo PLC EN 5.1

Fault message

Remedy

Cause

Description

No.

Remedy

Cause

Description

Display

x058

OH8

Motor temperature via inputs T1 and T2 is
too high.

Motor is thermally overloaded due to:

·

Impermissible continuous current

·

Frequent or too long acceleration
processes

·

Check drive dimensioning.

·

Switch off monitoring (C0585 = 3).

Terminals T1 and T2 are not connected

Connect PTC/temperature contact.

x061

CE0

Automation interface (AIF) communication
error

Faulty transfer of control commands via AIF.

·

Plug in the communication
module/keypad XT firmly, screw down, if
necessary.

·

Switch off monitoring (C0126 = 3).

x062

CE1

Communication error on the process data
input object CAN1_IN

CAN1_IN object receives faulty data or
communication is interrupted.

·

Check wiring at X4.

·

Check sender.

·

Increase monitoring time under
C0357/1, if necessary.

·

Switch off monitoring (C0591 = 3).

x063

CE2

Communication error on the process data
input object CAN2_IN

CAN2_IN object receives faulty data or
communication is interrupted.

·

Check wiring at X4.

·

Check sender.

·

Increase monitoring time under
C0357/2, if necessary.

·

Switch off monitoring (C0592 = 3).

x064

CE3

Communication error on the process data
input object CAN3_IN

CAN3_IN object receives faulty data or
communication is interrupted.

·

Check wiring at X4.

·

Check sender.

·

Increase monitoring time under
C0357/3, if necessary.

·

Switch off monitoring (C0593 = 3).

x065

CE4

BUS−OFF state of system bus (CAN)

The controller has received too many faulty
telegrams via the system bus (CAN) and has
disconnected from the bus.

·

Check wiring at X4: Is the bus correctly
terminated?

·

Check shield connection of the cables.

·

Check PE connection.

·

Check bus load, reduce the baud rate if
necessary. (Observe the cable length!)

·

Switch off the monitoring (C0595 = 3).

x066

CE5

Time−out of system bus (CAN)
(communication error of gateway function)

For remote parameterisation (C0370,
C0371) via system bus (CAN):

·

Slave does not respond.

·

Communication monitoring time has
been exceeded.

·

Check wiring of system bus (CAN).

·

Check CAN bus configuration.

0070

U15

Undervoltage of internal 15 V voltage supply

Check voltage supply.

0071

CCr

System failure

Strong interference injection on the control
cables

Screen control cables

Ground or earth loops in the wiring

·

Check wiring

·

Check PE connection

After troubleshooting: Deenergise the
device completely (disconnect 24 V
supply, discharge DC bus)!

0072

PR1

Checksum error in parameter set 1
CAUTION: The Lenze setting is loaded
automatically!

·

Fault when loading a parameter set.

·

Interruption while transmitting the
parameter set via keypad.

·

Set the required parameters and store
them under C0003 = 1.

·

As to PLC devices, check the use of
pointers.

The stored parameters are incompatible
with the loaded software version.

Store the parameter set under C0003 = 1
first to allow for a faults reset.

0074

PEr

Program error

Error in the program flow

Send the parameter set (on floppy
disk/CD−ROM) with a detailed description of
the problem to Lenze.
After troubleshooting: Deenergise the
device completely (disconnect 24 V
supply, discharge DC bus)!

0075

PR0

Error in parameter set.

The operating system software has been
updated.

Storage of the Lenze setting C0003 = 1.

After troubleshooting: Deenergise the
device completely (disconnect 24 V
supply, discharge DC bus)!

x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP