Lp1 − monitoring of the motor phases, 9300 servo plc, System blocks – Lenze DDS Target 9300 Servo PLC V8.x User Manual

Page 89: 7 lp1 − monitoring of the motor phases

Advertising
background image

9300 Servo PLC

System blocks

2.12

MCTRL_MotorControl (node number 131)

2−83

L

9300 Servo PLC EN 5.1

2.12.17.7

LP1 − monitoring of the motor phases

This monitoring function checks if a motor phase has failed.

Note!

·

This monitoring function can only be used for asynchronous motors.

·

When this monitoring function is activated, the calculating time available for the user is
reduced.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x032 LP1

Motor phase failure

MCTRL_bMotorphaseFail_b

ь

ь

·

· Lenze setting

ü Setting possible

·

The monitoring limit is set under C0599.

·

The response is set under C0597.

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0597 MONIT LP1

3

Configuration of motor phase
monitoring (LP1)

0

TRIP

2

Warning

3

Off

C0599 Limit LP1

5

LP1 fault monitoring limit

0.01

{0.01 %}

10.00

Error acknowledgement

1. Check motor cables.

2. Execute TRIP−RESET.

Advertising