9300 servo plc, Ȧȧ ȡ ȣ, Ȧȧ ȣ ȥ – Lenze DDS Target 9300 Servo PLC V8.x User Manual

Page 83: System blocks, Forced ventilated or naturally ventilated motors

Advertising
background image

9300 Servo PLC

System blocks

2.12

MCTRL_MotorControl (node number 131)

2−77

L

9300 Servo PLC EN 5.1

Forced ventilated or naturally ventilated motors

Parameter setting

The following codes can be set for I

2

x t monitoring:

Code

Meaning

Value range

Lenze setting

C0066

Display of the I

2

x t load of the motor

0 ... 250 %

C0120

Threshold: Triggering of error "OC6"

0 ... 120 %

0 %

C0127

Threshold: Triggering of error "OC8"

0 ... 120 %

0 %

C0128

Thermal motor time constant

0.1 ... 50.0 min

5.0 min

C0606

Response to error "OC8"

TRIP, warning, off

Warning

Calculate release time and I

2

x t load

Formula for release time

Information

t

+ * ( t ) ln

ȧȧ

ȡ
Ȣ

1

*

z

) 1

ǒ

I

Mot

I

N

Ǔ

2

100

ȧȧ

ȣ
Ȥ

I

Mot

Actual motor current (C0054)

I

r

Rated motor current (C0088)

t

Thermal motor time constant (C0128)

z

Threshold value in C0120 (OC6) or C0127 (OC8)

Formulae for I

2

x t load

Information

L(t)

+

ǒ

I

Mot

I

N

Ǔ

2

100%

ǒ

1

* e

*t

t

Ǔ

L(t)

Chronological sequence of the I

2

x t load of the motor

(Display: C0066)

I

Mot

Actual motor current (C0054)

Ir

Rated motor current (C0088)

t

Thermal motor time constant (C0128)

If the controller is inhibited, the I

2

x t load is reduced:

L(t)

+ L

Start

e

*

t

t

Ǹ

L

Start

I

2

x t load before controller inhibit

If an error is triggered, the value corresponds to the threshold value set
in C0120 (OC6) or C0127 (OC8).

Read release time in the diagram

Diagram for detecting the release times for a motor with a thermal motor time constant of 5 minutes
(Lenze setting C0128):

I

= 3 × I

Mot

N

0

50

100

120

0

100

200

300

400

500

600

700

800

900

1000

t [s]

L [%]

I

= 2 × I

Mot

N

I

= 1.5 × I

Mot

N

I

= 1 × I

Mot

N

9300STD105

Fig. 2−28

I

2

× t−monitoring: Release times for different motor currents and trigger thresholds

I

Mot

Actual motor current (C0054)

I

r

Rated motor current (C0088)

L

I

2

x t load of the motor (display: C0066)

T

Time

Advertising