9300 servo plc, Appendix – Lenze DDS Target 9300 Servo PLC V8.x User Manual

Page 141

Advertising
background image

9300 Servo PLC

Appendix

3.6

Code table

3−135

L

9300 Servo PLC EN 5.1

Code

Information

Possible settings

LCD

Code

Information

Selection

Lenze

LCD

C0362 Sync cycle

g

System bus: Time interval between 2 sync telegrams
(in preparation)

1

{1 ms}

30

C0363 Sync corr

1

System bus: Sync correction increments

1

0.2

ms/ms

2

0.4

ms/ms

3

0.6

ms/ms

4

0.8

ms/ms

5

1.0

ms/ms

C0365 DIS:CAN active

g

Input signal CAN active

0

CAN not active

1

CAN active

C0366 Sync response

1

System bus: Sync response

0

No response

1

Response to sync

No response
PLC responds to a sync telegram by sending the
CAN1_OUT object.

C0367 Sync Rx Id

128

System bus: Sync Rx identifier
Receive identifier of the sync telegram.

1

{1}

256

C0368 Sync Tx Id

128

System bus: Sync Tx identifier
Send identifier of the sync telegram.

1

{1}

256

C0369 Sync Tx time

0

System bus: CAN sync send telegram cycle

·

A sync telegram with the identifier of C0368 is sent
with the set cycle time.

0

{1}

65000

0 = Off

C0370 Gateway addr.

0

System bus: Activate SDO gateway remote
parameterisation
The SDO gateway cannot be used to read out codes
>C2000 or codes of the Inverter Drives 8400 and Servo
Drives 9400.

·

When selecting a setting

¹0, all code read/write

accesses will be redirected to the system bus device
with the corresponding node address.

·

The codes are accessed via the SDO1 parameter
channel of the target device.

0

{1}

63

0 = remote parameter setting deactivated

C0381 HeartProTime

0

System bus: Heartbeat (slave): HeartbeatProducerTime
Time interval for sending the "heartbeat" message.

·

Only relevant for setting C0352 = 3.

·

Additional information about the "heartbeat" function
can be found in the Manual for the function library
LenzeCanDSxDrv.lib.

0

{1 ms}

65535

C0382 GuardTime

0

System bus: Node Guarding (slave): NodeGuardTime
Time interval for the status request from the master.

·

Only relevant for setting C0352 = 4.

·

Additional information about the "node guarding"
function can be found in the Manual for the function
library LenzeCanDSxDrv.lib.

0

{1 ms}

65535

Advertising