L

9300 Servo PLC EN 5.1

Fault message

Remedy

Cause

Description

No.

Remedy

Cause

Description

Display

x240

ovrTrans
Queue

"Free CAN objects" error

Overflow of the transmit request memory

·

Reduce the number of transmit
requests.

·

Prolong the cycle time.

x241

ovr Receive

Too many receive telegrams

Reduce the number of telegrams on the
system bus (CAN).

x250

2.Flash Err

Error when the FLASH memory is accessed

The PLC program tries to access
non−available or defect FLASH memory

Make sure that the PLC has the
corresponding FLASH memory. If not,
please contact Lenze.
After troubleshooting: Deenergise the
device completely (disconnect 24 V
supply, discharge DC bus)!

x251

AddData CsErr

Error during FLASH memory access

Check sum error occurred when loading
data into the FLASH memory

Check the checksum of the file to be loaded
and repeat the data transfer.

x252

AddData DlErr

Error during FLASH memory access

An error occurred when downloading the
data into the FLASH memory (e.g. time−out,
transmission error, mains failure during
transmission)

Check/repeat data transfer.

x260

Err Node
Guard

"Life guarding event"

The controller configured as a CAN slave
does not receive a "Node Guarding"
telegram from the CAN master within the
"Node Life Time".

·

Check wiring at X4.

·

Check CAN configuration.

·

Ensure that "node guarding" has been
activated in the CAN master

·

Adapt the "node life time" (C0383) to
CAN master setting.

x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP