9300 servo plc, Appendix, 6 code table – Lenze DDS Target 9300 Servo PLC V8.x User Manual

Page 147

Advertising
background image

9300 Servo PLC

Appendix

3.6

Code table

3−141

L

9300 Servo PLC EN 5.1

Code

Information

Possible settings

LCD

Code

Information

Selection

Lenze

LCD

C0585 MONIT OH8

3

Monitoring configuration: Motor temperature
(Motor temperature across T1/T2 too high)

·

Temperature monitoring via PTC input

0

TRIP

2

Warning

3

Off

C0586 MONIT SD2

0

Monitoring configuration: Resolver error

0

TRIP

2

Warning

3

Off

C0587 MONIT SD3

3

Monitoring configuration: Encoder error at X9/pin 8

0

TRIP

2

Warning

3

Off

C0588 MONIT H10/H11

3

Monitoring configuration: Temperature sensors
(Heatsink temperature/temperature inside the controller)

0

TRIP

2

Warning

3

Off

C0591 MONIT CE1

3

System bus: Monitoring configuration
CAN1_IN communication error (CE1)

0

TRIP

2

Warning

3

Off

C0592 MONIT CE2

3

System bus: Monitoring configuration
CAN2_IN communication error (CE2)

0

TRIP

2

Warning

3

Off

C0593 MONIT CE3

3

System bus: Monitoring configuration
CAN3_IN communication error (CE3)

0

TRIP

2

Warning

3

Off

C0594 MONIT SD6

à

Monitoring configuration: Motor temperature sensor error
(X7 or X8)

à

Dependent on C0086

0

TRIP

2

Warning

3

Off

C0595 MONIT CE4

3

System bus: Monitoring configuration
"BusOffState" (CE4)

0

TRIP

2

Warning

3

Off

C0596 NMAX limit

5500

Monitoring configuration: Max. speed of the machine

0

{1 rpm}

16000

C0597 MONIT LP1

3

Configuration of motor phase monitoring (LP1)

0

TRIP

2

Warning

3

Off

·

Setting of the monitoring limit via C0599

C0598 MONIT SD5

3

Monitoring configuration: Master current at X6/1, 2
(Master current < 2 mA)

0

TRIP

2

Warning

3

Off

C0599 Limit LP1

5

LP1 fault monitoring limit

0.01

{0.01 %}

10.00