9300 servo plc, System blocks, 6 lu − undervoltage monitoring – Lenze DDS Target 9300 Servo PLC V8.x User Manual

Page 88

Advertising
background image

2.12

MCTRL_MotorControl (node number 131)

9300 Servo PLC

System blocks

2−82

L

9300 Servo PLC EN 5.1

2.12.17.6

LU − undervoltage monitoring

This function monitors the DC bus and protects the controller.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x030 LU

Undervoltage

MCTRL_bUndervoltage_b

·

· Lenze setting

ü Setting possible

The monitoring responds if the DC−bus voltage at the terminals +U

G

and −U

G

falls below a switch−off

threshold dependent on C0173 and it remains active until the corresponding switch−on threshold has
again been exceeded.

·

The DC−bus voltage is set under C0173

(

^ 2−80)

.

·

The switch−off and switch−on thresholds dependent on C0173 can be gathered from the
following table:

Setting of C0173

Switch−off threshold

Switch−on threshold

0

Mains < 400 V; with or without brake unit

285 V

430 V

1

Mains = 400 V; with or without brake unit

285 V

430 V

2

Mains = 460 V; with or without brake unit

328 V

473 V

3

Mains = 480 V; without brake unit

342 V

487 V

4

Mains = 480 V; with brake unit

342 V

487 V

·

The switch−off threshold defines the voltage level of the DC−bus voltage, at which the pulse
inhibit is activated.

Tip!

If the undervoltage lasts longer than 3 s or if the drive is powered up, this is entered into the fault
memory.

·

This can be the case if the control module is supplied externally via the terminals X5/39 and
X5/59 and the mains is switched off.

·

If the undervoltage has been eliminated (reconnection to the mains), the entry is not updated
in the fault memory but deleted because this is not an error but a controller status.

Undervoltages which last for less than 3 s are interpreted as a fault (e.g. power system fault) and
entered into the fault memory. In this case the fault memory is updated.

Advertising