Technical Data

Electrical Specifications applicable to all models:

Acceleration Time Range (Zero to Max Speed)

0.1 … 5x10

6

RPM/sec

Deceleration Time Range (Max Speed to Zero)

0.1 … 5x10

6

RPM/sec

Speed Regulation (typical)

± 1 RPM

Input Impedance (AIN+ to COM and AIN+ to AIN-)

47 k

Power Device Carrier Frequency (sinusoidal commutation)

8, 16 kHz

Power Supply (max)

+5 VDC @ 300 mA

Maximum Encoder Feedback Frequency

2.1 MHz (per channel)

Maximum Output Frequency (to motor)

400 Hz

Resolver Carrier Frequency

4.5 - 5.5kHz (5kHz nom)

Resolver Turns Ratio: Reference to SIN/COS signal

2:1

Resolver Voltage

10V peak to peak

Maximum Resolver Feedback Speed

6500 rpm

2.2

Power Ratings

Type

(1)

Output Power

at Rated Output

Current (8kHz)

(2)

Leakage Current

Power Loss at

Rated Output

Current

(8kHz)

Power Loss at

Rated Output

Current

(16 kHz)

(3)

Units

kVA

mA

Watts

Watts

E94_020S1N_~

0.8

Typically >3.5 mA.

Consult factory for

applications requiring

<3.5 mA.

19

21

E94_040S1N_~

1.7

29

30

E94_020S2F_~

0.8

19

21

E94_040S2F_~

1.7

29

30

E94_080S2F_~

3.3

61

63

E94_100S2F_~

4.2

80

85

E94_020Y2N_~

0.8

19

21

E94_040Y2N_~

1.7

29

30

E94_080Y2N_~

3.3

61

63

E94_120Y2N_~

5.0

114

129

E94_180T2N_~

7.5

171

195

E94_020T4N_~

1.7

31

41

E94_040T4N_~

3.3

50

73

E94_060T4N_~

5.0

93

122

E94_090T4N_~

7.5

138

182

(1)

The first “_” equals “P” for the Model 940 encoder based drive

or “R” for the Model 941 resolver based drive.

The second “_” equals “E” for incremental encoder (must have E94P drive)

or “R” for the standard resolver (must have E94R drive).

The last digit “~” equals “M” for MV OnBoard and no ISO 13849-1 circuit or “S” for MV OnBoard plus the ISO 13849-1 circuit.

(2)

At 240 VAC line input for drives with suffixes “S1N”, “S2F”, “Y2N”. At 480 VAC line input for drives with suffixes “T4N”.
a. The output power is calculated from the formula: output kVA = [( 3) x U

LL

x I

rated

] / 1000

b. The actual output power (kW) depends on the motor in use due to variations in motor rated voltage, rated speed and power factor, as well as actual max

operating speed and desired overload capacity.

c. Typical max continuous power (kW) for PM servo motors run 50-70% of the kVA ratings listed.

(3)

At 16 kHz, de-rate continuous current by 17%

Advertising