Lenze TCF Series User Manual

Page 12

Advertising
background image

MODEL

NUMBER

(NOTE 1)

FOR MOTORS

RATED

INPUT (50-60 Hz)

OUTPUT

HEAT LOSS

(WATTS)

(NOTE 5)

INPUT

PHASE

CURRENT

(AMPS)

POWER

(kVA)

CURRENT

(AMPS)

HP

kW

TF400 SERIES (NOTE 3)

400 / 480 Vac

0 - 400 / 460 Vac

TF405

0 .5

0 .37

3

1 .6 / 1 .4

1 .1

1 .3 / 1 .1

26

TF410

1

0 .75

3

2 .9 / 2 .5

2 .1

2 .4 / 2 .1

40

TF415

1 .5

1 .1

3

4 .0 / 3 .6

3 .0

3 .4 / 3 .0

56

TF420

2

1 .5

3

4 .6 / 4 .0

3 .3

3 .9 / 3 .4

67

TF430

3

2 .2

3

6 .2 / 5 .4

4 .5

5 .5 / 4 .8

100

TF450

5

4 .0

3

10 .6 / 8 .8

7 .1

9 .4 / 7 .8

168

TF475

7 .5

5 .5

3

14 .2 / 12 .4

10 .3

12 .6 / 11 .0

254

TF4100

10

7 .5

3

18 .1 / 15 .8

13 .1

16 .1 / 14 .0

310

TF500 SERIES (NOTE 4)

480 / 590 Vac

0 - 460 / 575 Vac

TF510

1

0 .75

3

2 .2 / 2 .0

1 .9 / 2 .0

1 .9 / 1 .7

40

TF520

2

1 .5

3

4 .0 / 3 .5

3 .3 / 3 .6

3 .4 / 3 .0

67

TF530

3

2 .2

3

4 .7 / 4 .7

3 .9 / 4 .8

4 .2 / 4 .2

100

TF550

5

3 .7

3

7 .4 / 7 .4

6 .1 / 7 .5

6 .6 / 6 .6

168

TF575

7 .5

5 .5

3

11 .2 / 11 .2

9 .3 / 11 .4

9 .9 / 9 .9

254

TF5100

10

7 .5

3

13 .7 / 13 .7

11 .4 / 14 .0

12 .2 / 12 .2

310

NOTE 1: Refer to Section 3 for model number breakdown .
NOTE 3: The higher current ratings are for 400 Vac input and the lower current ratings are for 480 Vac input .
NOTE 4: The higher current ratings are for 480 Vac input and the lower current ratings are for 590 Vac input .
NOTE 5: Values are worst-case (not typical) for 4kHz carrier frequency at full speed and full load

8

Advertising