P28

FIXED BOOST

FIXED BOOST is active only in V/Hz mode (refer to Parameter 80), and increases starting
torque by increasing the output voltage when operating below half of the base frequency,
which increases the V/Hz ratio . The factory default setting depends on HP rating, as shown
in the following table .

HP

DEFAULT

HP

DEFAULT

0 .5 - 1

2 .0%

5

1 .2%

1 .5 - 2

1 .8%

7 .5

1 .0%

3

1 .5%

10

1 .0%

P29

ACCELERATION BOOST

ACCELERATION BOOST is active only in V/Hz mode (refer to Parameter 80), and helps
accelerate high-inertia loads . During acceleration the output voltage is increased to increase
motor torque . Once the motor reaches the new speed setpoint the boost is turned off .
P30

SLIP COMPENSATION

SLIP COMPENSATION is active only in V/Hz mode (refer to Parameter 80) and is used
to counteract changes in motor speed (slip) caused by changes in load . In a standard
AC induction motor, the shaft speed decreases as load increases and increases as load
decreases . By increasing or decreasing the output frequency in response to an increasing or
decreasing load, the slip is counteracted and speed is maintained . Most standard NEMA B
motors have a 3% slip rating .
P31-P37 PRESET SPEED #1 - #7
Preset speeds are activated by contact closures between TB-4 and TB-13A (or 13D), 13B and
13C . The TB-13 terminals must be programmed as preset speed selects using Parameters
10, 11, 12 and 49 . Preset Speeds #2 and #4 are also used when the drive is in JOG mode .
Refer to Parameters 11 and 12 . Preset speeds are not available in Vector Torque mode .

NOTE
Preset speeds can operate below the frequency defined by MINIMUM
FREQUENCY (Parameter 23) . The range of adjustment for the preset speeds
is from 0 Hz to MAXIMUM FREQUENCY (Parameter 24) .

46