Lenze TCF Series User Manual

Page 47

Advertising
background image

P13

TB-15 OPEN COLLECTOR OUTPUT

This selects the status indication for the open-collector output at TB-15, and has the same
selections as Parameter 6 - TB-14 OPEN COLLECTOR OUTPUT .
P14

CONTROL

This selects the source of START/STOP and direction commands .

01 TERMINAL STRIP ONLY: The drive will only respond to START/STOP and

direction commands from the terminal strip .

02 REMOTE KEYPAD ONLY: The drive will only respond to START/STOP and

direction commands from the optional remote keypad .

03 TERMINAL STRIP OR REMOTE KEYPAD: Terminal TB-13A, TB-13C, or

TB-13D can be used to select terminal strip control or remote keypad control .
Refer to Parameters 10, 12, and 49 .

NOTE
The STOP button on the optional remote keypad is always active as long as
the serial link remains intact .

P15

SERIAL LINK

This parameter configures the drive for Modbus RTU serial communications . The options are
listed by baud rate, number of data bits, parity, number of stop bits and whether the watchdog
timer is enabled or disabled .

WARNING!
Controlling the drive from the serial link without the watchdog timer could
cause damage to equipment and/or injury to personnel!

The watchdog timer will stop the drive after 10 seconds of no serial activity to safeguard
against a failed serial link . During set-up or troubleshooting it may be useful to disable the
watchdog timer but is it not recommended to run normally without the watchdog timer .

01 DISABLED: Disables the serial link

02 9600, 8, N, 2 - ENABLED WITH TIMER

03 9600, 8, N, 2 - ENABLED WITHOUT TIMER

04 9600, 8, E, 1 - ENABLED WITH TIMER

05 9600, 8, E, 1 - ENABLED WITHOUT TIMER

06 9600, 8, O, 1 - ENABLED WITH TIMER

07 9600, 8, O, 1 - ENABLED WITHOUT TIMER

43