7 .3 input wire size requirements, 7 .4 installation according to emc requirements – Lenze TCF Series User Manual

Page 17

Advertising
background image

7 .3

INPUT WIRE SIZE REQUIREMENTS

INPUT WIRE SIZE REQUIREMENTS

208/240 Vac, 1 phase

208/240 Vac, 3 phase

400/480 Vac, 3 phase

480/590 Vac, 3 phase

MODEL AWG mm2

MODEL AWG mm2

MODEL AWG mm2

MODEL AWG mm2

TF205Y

14

1 .5

TF205Y

14

1 .5

TF405

14

1 .5

TF210Y

14

1 .5

TF210(Y)

14

1 .5

TF410

14

1 .5

TF510

14

1 .5

TF215Y

12

2 .5

TF215(Y)

14

1 .5

TF415

14

1 .5

TF220Y

12

2 .5

TF220(Y)

14

1 .5

TF420

14

1 .5

TF520

14

1 .5

TF230Y

10

4 .0

TF230(Y)

12

2 .5

TF430

14

1 .5

TF530

14

1 .5

TF250

10

4 .0

TF450

14

1 .5

TF550

14

1 .5

TF275

8

6 .0

TF475

12

2 .5

TF575

14

1 .5

TF2100

8

10

TF4100

10

4 .0

TF5100

12

2 .5

7 .4

INSTALLATION ACCORDING TO EMC REQUIREMENTS

This drive can be installed to meet the European standards for Electromagnetic Compatibility
(EMC) requirements . These requirements govern the permissible electromagnetic emissions
and immunity, both radiated and conducted, of a drive system .

The EMC requirements apply to the final installation in its entirety, not to the individual
components used . Because every installation is different, the recommended installation
should follow these guidelines as a minimum . Additional equipment (such as ferrite core
absorbers on power conductors) or alternative wiring practices may be required to meet
conformance in some installations .

Filter: The input to the drive (or group of drives) must include a filter to reduce the electrical
noise reflected back to the AC Line . To meet the industrial standards set by the EU, EN 61800-
3 for conducted emissions and EN 55011 for radiated emissions to class A compliance, the
drive must be installed with an appropriate filter and a maximum motor cable length of 10m .

EMC
Compliance with EN 61800-3/A11

SM01 1

B

C

D

A

E

Installation: Shielded cable must be used for all control and power
cables and exposed wiring must be kept as short as possible .

A Screen clamps

B Control cable

C Low-capacitance motor cable

(core/core < 75 pF/m, core/screen < 150 pF/m)

D Electrically conductive mounting plate

E Filter

13