7 .2

INPUT FUSING & DISCONNECT REQUIREMENTS

A circuit breaker or a disconnect switch with fuses must be provided in accordance with the
National Electric Code (NEC) and all local codes . Refer to the following tables for proper
fuse/circuit breaker ratings and wire sizes .

INPUT FUSE & CIRCUIT BREAKER RATINGS

208/240 Vac, 1 phase 208/240 Vac, 3 phase 400/480 Vac, 3 phase

480/590 Vac, 3 phase

MODEL

RATING

MODEL

RATING

MODEL

RATING

MODEL

RATING

TF205Y

10 A

TF205Y

10 A

TF405

10 A

TF210Y

15 A

TF210(Y)

10 A

TF410

10 A

TF510

10 A

TF215Y

20 A

TF215(Y)

12 / 10 A

TF415

10 A

TF220Y

25 / 20 A

TF220(Y)

15 / 12 A

TF420

10 A

TF520

10 A

TF230Y

30 / 25 A

TF230(Y)

20 / 15 A

TF430

10 A

TF530

10 A

TF250

30 / 25 A

TF450

15 A

TF550

12 A

TF275

45 / 40 A

TF475

20 A

TF575

20 A

TF2100

50 / 50 A

TF4100

30 / 25 A

TF5100

20 A

NOTE
• Applicable national and local electrical codes take precedence over

recommendations in these tables .

• Use UL Class CC fast-acting, current limiting type fuses . Select fuses

with low I2T values, rated at 200,000 AIC . Recommended fuses are
Bussman KTK-R, JJN, and JJS . Similar fuses with equivalent ratings by
other manufacturers may also be acceptable .

WARNING!
This product can cause a DC current in the protective conductor . Where
a residual current device (RCD) is used for protection in case of direct or
indirect contact, only an RCD of Type B is allowed on the supply side of
this product . Otherwise, another protective measure shall be applied, such
as separation from the environment by double or reinforced insulation, or
isolation from the supply system by a transformer .

Observe the following when using RCDs:

1 . Only install the RCD between the supply mains and drive controller .
2 . The RCD can be activated by:

capacitive leakage currents between the cable screens during
operation (especially with long, screened motor cables)

connecting several drives to the mains at the same time

additional RFI filters