10 control wiring – Lenze TCF Series User Manual

Page 20

Advertising
background image

10

CONTROL WIRING

10 .1

CONTROL WIRING VS . POWER WIRING

External control wiring MUST be run in a separate conduit away from all other input and
output power wiring . If control wiring is not kept separate from power wiring, electrical noise
may be generated on the control wiring that will cause erratic drive behavior . Use twisted
wires or shielded cable grounded at the drive chassis ONLY . Recommended control wire is
Belden 8760 or 8770, or equivalent .

NOTE
Control terminals provide basic isolation (insulation per EN 61800-5-1) .
Protection against contact can only be assured by additional measures e .g .
supplemental insulation .

Strip off 0 .20 to 0 .25 inches (5 to 6 mm) of insulation for control wiring, and torque the
terminals to 2 lb-in (0 .2 Nm) . Be careful not to overtorque the terminals, as this will cause
damage to the terminal strip . This is not covered under warranty and can only be repaired by
replacing the control board .

10 .2

TB-2 AND TB-4

The TB-2 terminals are the circuit common for the analog input and analog output functions .
The TB-4 terminals are the reference for all of the digital inputs (TB-1, 13A, 13B, 13C, and
13D) . The digital inputs are active-high as standard, but can be configured for active-low
during initial set-up . Refer to APPENDIX B - INPUT ASSERTION LEVEL . When set for
active-high, TB-4 is at +12 VDC .

NOTE
TB-2 may be connected to chassis ground if noise is a concern . TB-2 must

be connected to chassis ground when using serial communications .

10 .3

SURGE SUPPRESSION ON RELAYS

Current and voltage surges and spikes in the coils of contactors, relays, solenoids, etc, near
or connected to the drive, can cause erratic drive operation . Therefore, a snubber circuit
should be used on coils associated with the drive . For AC coils, snubbers should consist
of a resistor and a capacitor in series across the coil . For DC coils, a free-wheeling or
flyback diode should be placed across the coil . Snubbers are typically available from the
manufacturer of the device .

10 .4

START/STOP CONTROL

There are various control schemes that allow for 2-wire and 3-wire Start/Stop circuits . Refer
to the wiring diagrams in Section 11 - TCF CONTROL WIRING DIAGRAMS

16

Advertising