DESCRIPTION OF PARAMETERS

P01

LINE VOLTAGE SELECTION

This calibrates the drive for the actual applied input voltage, and can be set to HIGH (01) or
LOW (02) . Refer to the table below for the proper setting depending on the input voltage .

MODEL

RATED INPUT

VOLTAGE

INPUT

PHASE

APPLIED INPUT

VOLTAGE

PARAMETER

SETTING

TF200Y

208 / 240 Vac

1 or 3

220 - 240 Vac

HIGH (01)

1 or 3

200 - 208 Vac

LOW (02)

TF200

208 / 240 Vac

3

220 - 240 Vac

HIGH (01)

3

200 - 208 Vac

LOW (02)

TF400

400 / 480 Vac

3

440 - 480 Vac

HIGH (01)

3

380 - 415 Vac

LOW (02)

TF500

480 / 590 Vac

3

575 - 600 Vac

HIGH (01)

3

460 - 480 Vac

LOW (02)

NOTE
If this parameter is changed while the drive is running, the new value will not
take effect until the drive is stopped .

P02

CARRIER FREQUENCY

This sets the switching rate of the output IGBT’s . Increasing the carrier frequency will result
in less audible motor noise . Available settings are: 2 kHz, 4 kHz, and 8 kHz .

The TCF drive is fully rated up to 4 kHz carrier frequency . If the 8 kHz carrier frequency is
selected, the drive’s ambient temperature rating must be de-rated to 43°C, OR the output
current rating must be de-rated to 92% .

NOTE
• If the drive's heatsink temperature gets too hot while running, the carrier

frequency will automatically shift to a lower value to increase efficiency
and lower heat generation .

• If this parameter is changed while the drive is running, the change will not

take effect until the drive is stopped .