15 description of parameters – Lenze TCF Series User Manual
Page 40
![background image](/manuals/566128/40/background.png)
15
DESCRIPTION OF PARAMETERS
P01
LINE VOLTAGE SELECTION
This calibrates the drive for the actual applied input voltage, and can be set to HIGH (01) or
LOW (02) . Refer to the table below for the proper setting depending on the input voltage .
MODEL
RATED INPUT
VOLTAGE
INPUT
PHASE
APPLIED INPUT
VOLTAGE
PARAMETER
SETTING
TF200Y
208 / 240 Vac
1 or 3
220 - 240 Vac
HIGH (01)
1 or 3
200 - 208 Vac
LOW (02)
TF200
208 / 240 Vac
3
220 - 240 Vac
HIGH (01)
3
200 - 208 Vac
LOW (02)
TF400
400 / 480 Vac
3
440 - 480 Vac
HIGH (01)
3
380 - 415 Vac
LOW (02)
TF500
480 / 590 Vac
3
575 - 600 Vac
HIGH (01)
3
460 - 480 Vac
LOW (02)
NOTE
If this parameter is changed while the drive is running, the new value will not
take effect until the drive is stopped .
P02
CARRIER FREQUENCY
This sets the switching rate of the output IGBT’s . Increasing the carrier frequency will result
in less audible motor noise . Available settings are: 2 kHz, 4 kHz, and 8 kHz .
The TCF drive is fully rated up to 4 kHz carrier frequency . If the 8 kHz carrier frequency is
selected, the drive’s ambient temperature rating must be de-rated to 43°C, OR the output
current rating must be de-rated to 92% .
NOTE
• If the drive's heatsink temperature gets too hot while running, the carrier
frequency will automatically shift to a lower value to increase efficiency
and lower heat generation .
• If this parameter is changed while the drive is running, the change will not
take effect until the drive is stopped .
36