13 programming the tcf drive – Lenze TCF Series User Manual

Page 32

Advertising
background image

13

PROGRAMMING THE TCF DRIVE

The drive may be programmed by one of three methods: using the three buttons and 3-digit
LED display on the front of the drive, programming the Electronic Programming Module (EPM)
using the optional EPM Programmer, and through a serial link using serial communications .
This section describes programming the drive using the buttons and display .

NOTE
Refer to Appendix A for information on operating the TCF Series drive in
vector mode .

BUTTONS

Mode

Display

To enter the PROGRAM mode to access the parameters, press the Mode button . This will
activate the PASSWORD prompt (if the password has not been disabled) . The display will
read “00” and the upper decimal point will be blinking as shown below .

Press Mode

Display reads "00"

Upper decimal point blinks

Use the s and t buttons to scroll to the password value (the factory default password
is “225”) and press the

Mode button . Once the correct password value is entered, the

display will read "P01", which indicates that the PROGRAM mode has been accessed at
the beginning of the parameter menu (P01 is the first parameter) .

Use s and t to scroll to the

password value

Press mode to enter password

Parameter menu is accessed at

the first parameter

NOTE
If the display flashes “Er”, the password was incorrect, and the process to
enter the password must be repeated .

28