Technical data – Lenze 931W User Manual

Page 16

Advertising
background image

Technical data

Rated data

General data and operating conditions

3

16

GHB 13.0002-EN 3.1

3.3

Rated data

3.3.1

General data and operating conditions

The following standards and operating conditions are generally valid for 931M and

931W servo inverters:

Conformity

CE

Low-Voltage Directive 73/23/EEC

Regulations

Requirements in accordance with IEC/EN 61800-3 (category C3)

Climatic conditions

Air humidity max. 90 % without condensation

Cooling

Passively via housing surface and heatsink

Permissible temperature ranges

Transport

-25 °C... +70 °C

Storage

-25 °C... +70 °C

Operation

0 °C ... +40 °C

Internal ambient temperature

T

electronics

> 70 °C: Power derating

Disconnection at T

electronics

> 78 °C

Permissible installation height

0 ... 1000 m amsl

above 1000 m amsl, reduce the rated output

current by 5 %/1000 m

Mounting position

Every mounting position and mounting arrangement is permissible

(see restriction)

Mounting clearances

above/below

≥ 50 mm

sidewise

≥ 50 mm

Type of protection

IP 54

DC bus system

Possible with restrictions

Explanation: Restrictions for DC bus systems

ƒ

When supplying several 931M or 931W devices with DC voltage from a DC bus

system, ensure that the permissible voltage limits for the DC bus are observed when

power is consumed or fed back by the inverters.

ƒ

We recommend to use slow-blowing DC fuses to fuse inverters in larger DC bus

systems.

Explanation: restrictions concerning the mounting position

ƒ

In principle, every mounting position is permissible. The manufacturer recommends

a vertical arrangement of the cooling ribs of the heatsink. For mounting positions

with a non-vertical arrangement of the cooling ribs, the free convection is negatively

influenced. In this case, a power derating of the drive due to the decreased cooling

power may be required.

0 V (low) and 24 V (high) are used for the digital inputs and outputs. Here, the local CAN

communication is an exception, using a lower voltage level (5 V). The digital inputs and

outputs are short-circuit-proof, whereas the local CAN interface is not resistant to

short-circuits.
The functions of the digital I/Os are listed in the below table. For more information, please

see the Software Manual.