Troubleshooting and fault elimination – Lenze 931W User Manual

Page 48

Advertising
background image

Troubleshooting and fault elimination

Fault elimination for errors / problems with regard to the handling of bus systems

8

48

GHB 13.0002-EN 3.1

8.3

Fault elimination for errors / problems with regard to the handling of bus systems

In order to be able to search for and eliminate errors and faults with regard to installation

and commissioning moreeasily,thedisplaywindow”Displayfieldbus”underthe”Service”

tab oftheoperating programis provided to you.If youobserve thedrive inthe ”Onlinelevel

1”, you can at the same time observe the control and status word of the drive and read and

communication objects and write to them (see Profibus, CAN bus Manual). Please observe

the access authorisations. If the operating program accesses to the drive within a higher

level (e.g. level service), the bus system is inhibited.

Error

Cause

Remedy

Communication faults

Bus plug not properly attached by snap

mechanism or incorrectly connected

Ensure faultless mounting of the bus

plugs

Missing bus terminating resistors

Check the terminating resistors of your

system

Bus address incorrectly set

Check the bus addresses of the nodes by

using the software (see Manual)

Baud rate of one or several nodes

incorrectly set

Check the baud rate of the nodes by using

the software (see Manual)

Last node does not log on on the bus

system.

Input and output interchanged. In

addition, terminating resistor activated.

The terminating resistor interrupts the

bus system to the output (X4.2)

Use input (X 4.1) for connecting the bus

system (see Manual)

Nodes after a drive do not log on on the

bus system

Terminating resistor activated in the

wrong place. The terminating resistor

interrupts the bus system to the output

(X4.2)

Deactivate terminating resistor of the

interrupting drive

Voltage error when connecting the supply

voltage

First the control voltage (24V), and

afterwards the power voltage (24, 42, 230

or 320 V) has been connected

Observe switch-on sequence. First power

(the control is supplied automatically at

the same time). Afterwards connect the

control voltage

Travel data set not executable

Settings in transmitted travel data set not

conflict-free

Check of the settings in the travel data set

Check of the software limit switch

(”System” tab) (use software limit switch

for positioning only)!

Check on whether the positioning target is

beyond the software limit switches

Drive cannot be activated via the bus

Access error. Bus system has no access to

the node

Check access of the ”Fluxx” operating

software to the drive (access max. online

level 1 for bus access!!!)

Drive can be started via the control word,

but does not accept any setpoints

Bus system does not have parameter

change rights (see ”Bus system” Manual)

Request parameter change rights via bus

system

Quick stop has been actuated via ”Fluxx”

software

The parameter change rights have to be

dispensed by the ”Fluxx”. Request

parameter change rights via bus system

again afterwards

Advertising